Skip to main content

Wire Size Calculator

By · Updated Sep 2026

Size copper or aluminum conductors from known current, installation conditions, and an optional resistance-only voltage-drop screen.

A
Enter actual operating current. Do not enter breaker rating or a current already multiplied by 125%.
THHN/THWN-2 uses the supported 2026 Table 310.16 raceway workflow. NM-B is a supported dry-location copper-cable workflow.
Aluminum is supported for THHN/THWN-2. CalcShed's NM-B model currently supports copper only.
Use the lowest applicable connected equipment/termination basis. Keep 60°C unless a 75°C basis has been confirmed for the installation.

Defaults: continuous portion 0 A · 86°F ambient · 3 CCC · rooftop off · voltage-drop screen off.

Share

How to Use

  1. Enter actual operating current - Use the known load current before any continuous-load multiplier. Do not enter the breaker rating or a current already enlarged by 125%.
  2. Choose the supported wiring method and material - THHN/THWN-2 supports copper or aluminum in this raceway model. CalcShed supports copper NM-B only in this release.
  3. Confirm the termination basis - For THHN/THWN-2, use 60°C unless the lowest applicable connected equipment/termination basis is confirmed for 75°C. NM-B uses its own 60°C final ceiling.
  4. Set installation conditions when needed - Advanced settings accept the continuous portion, governing ambient, current-carrying-conductor count, and the exact supported direct-sun rooftop condition.
  5. Optionally include voltage drop - The resistance-only planning screen can force a larger conductor for the entered run, but it does not replace detailed AC impedance analysis.

Quick answer

Wire size is selected by separate checks, not one blanket multiplier. The calculator first checks the applicable 60°C/75°C final-basis ampacity against noncontinuous current plus 125% of the continuous portion. Separately, it applies ambient and current-carrying-conductor factors to the 90°C conductor ampacity and checks that adjusted result against the actual load. Ordinary small-conductor protection limits remain a separate screen, and optional resistance-only voltage drop can require a larger conductor.

How the Wire Size Is Chosen

Actual + continuous loadM = I + 0.25C90°C ampacityambient × CCCFinal basis60°C / 75°C ceilingTwo ampacity checksfinal ≥ M and usable ≥ ISeparate constraintssmall-wire + optional VDFirst supported size passing every active check
The continuous-load sizing requirement is not applied a second time to the already adjusted ampacity. Small-conductor protection remains separate from thermal ampacity.

Continuous and Noncontinuous Current Use Two Checks

Let I be the actual total current and C the continuous portion of that total. The ordinary sizing requirement is M = I + 0.25C. The applicable final-basis ampacity must be at least M.

The corrected/adjusted conductor ampacity is checked separately against the actual total current I. Applying the extra 25% again to this adjusted-ampacity comparison can unnecessarily force a larger conductor.

The calculator does not model the 100%-rated-assembly exception or the separately installed connector exception. Those are outside this ordinary workflow.

Ambient Temperature, Rooftops, and Final Temperature Limits

The THHN/THWN-2 workflow uses the 90°C Table 310.16 value as the permitted correction/adjustment basis, then limits the final result by the applicable 60°C or 75°C connected-equipment/termination basis.

For the exact supported direct-sun rooftop case, raceway or cable less than 3/4 inch above the roof receives a 60°F temperature adder before the 90°C correction factor is selected. The calculator does not generalize this into every rooftop or cable installation.

NM-B uses its 90°C conductor rating for permitted correction/adjustment but cannot exceed the 60°C final ampacity in this model.

90°C Ambient Correction Examples

Ambient range90°C factor
78-86°F1.00
87-95°F0.96
96-104°F0.91
105-113°F0.87
114-122°F0.82
123-131°F0.76
132-140°F0.71

The engine includes the full supported -40°F through 185°F mapping. Fractional values are mapped conservatively to the next warmer published band; they are not rounded down.

Current-Carrying-Conductor Adjustment

Applicable CCC countAdjustment factor
1-3100%
4-680%
7-970%
10-2050%
21-3045%
31-4040%
41+35%

Neutral treatment depends on the actual circuit and load. Grounding and bonding conductors are not counted. The calculator accepts the applicable count you provide and does not infer code exceptions.

Equipment Termination Rating Is a Real Limit

The temperature basis is coordinated to the lowest applicable connected termination, conductor, or device. A higher insulation rating can be used for permitted correction/adjustment without turning a 60°C or 75°C equipment connection into a generic 90°C termination.

That is why the THHN/THWN-2 form asks for a confirmed 60°C or 75°C equipment termination basis rather than offering a generic 90°C option.

Worked Example A: Ordinary 20 A Copper THHN/THWN-2

CheckValueResult
Inputs20 A actual, 0 A continuous, 60°C basis, 86°F, 3 CCCNo correction or CCC reduction
14 AWG60°C ampacity 15 AFails 20 A load-sizing requirement
12 AWG60°C ampacity 20 A; 90°C basis 30 APasses ampacity and ordinary 20 A protection screen
Recommended size12 AWG copperSmallest supported size passing every active check

Worked Example B: 40 A Fully Continuous with 4 CCC

CheckValueResult
Load sizing requirementI = 40 A, C = 40 A → M = 50 AFinal-basis ampacity must be at least 50 A
8 AWG final basis75°C ampacity = 50 APasses the M check
8 AWG adjusted basis55 A × 0.80 = 44 A44 A ≥ actual 40 A load
Recommended size8 AWG copperComparing 44 A against 50 A again would apply the continuous-load increase twice

Worked Example C: Voltage Drop Governs

ConductorTable 8 resistance at 75°C120 V, 20 A, 100 ft one-way
12 AWG Cu1.98 Ω/kft7.92 V · 6.60%
10 AWG Cu1.24 Ω/kft4.96 V · 4.13%
8 AWG Cu0.778 Ω/kft3.11 V · 2.59%

Ampacity alone selects 12 AWG in this example. With the 3% resistance-only planning target enabled, 8 AWG becomes the first supported size that passes both ampacity and voltage drop.

Worked Example D: NM-B 60°C Ceiling

Check10 AWG copper NM-B
Actual load30 A
90°C correction/adjustment basis40 A
Final NM-B ceiling30 A at 60°C
Ordinary small-conductor protection screen30 A
Recommended size10 AWG Cu NM-B

Selection Logic

For each supported conductor size, the calculator keeps thermal ampacity, protection, and optional voltage drop as separate checks:

Load sizing requirement = M = actual current I + 0.25 × continuous portion C
Adjusted ampacity = A90 × 90°C ambient correction factor × CCC adjustment factor
Allowable ampacity = Minimum of adjusted ampacity and applicable final 60°C/75°C ceiling
Thermal pass = Final-basis ampacity ≥ M AND allowable adjusted ampacity ≥ I
Ordinary small-conductor protection = Separate 240.4(D) screen for supported 14/12/10 AWG cases; it does not replace thermal ampacity
DC / single-phase resistance-only VD = VD = 2 × I × R × one-way distance ÷ 1000
Balanced three-phase resistance-only VD = VD = √3 × I × R × one-way distance ÷ 1000
Pick rule = Return the first supported AWG/kcmil size that passes every active check

Internal comparisons use unrounded values. Display rounding happens only after the conductor has been selected.

2026 NEC and Physical-Data Sources

  • Connected termination/device temperature limits and the use of higher conductor temperature ratings for permitted correction/adjustment are based on 110.14(C).NFPA 70 (2026) 110.14(C)
  • The branch-circuit two-test continuous/noncontinuous conductor structure is based on 210.19(A); the feeder analogue used for this ordinary model is 215.4(A).NFPA 70 (2026) Articles 210 and 215
  • Ordinary small-conductor protection limits are kept separate from Table 310.16 thermal ampacity values.NFPA 70 (2026) 240.4(D)
  • Ampacity, ambient correction, current-carrying-conductor adjustment, neutral treatment, grounding/bonding count treatment, and the supported rooftop adder are based on Article 310.NFPA 70 (2026) 310.15 and Table 310.16
  • Copper NM-B in this calculator uses the 334.80 90°C adjustment/correction basis with a 60°C final ceiling. Other NM conductor materials recognized by the NEC are deliberately outside CalcShed's current NM-B support.NFPA 70 (2026) 334.80 / 334.104
  • The optional voltage-drop screen uses Chapter 9 Table 8 stranded-conductor DC resistance at 75°C. Table 9 demonstrates why AC resistance, reactance, arrangement, frequency, and power factor can require a more detailed model.NFPA 70 (2026) Chapter 9 Tables 8 and 9

Next Steps

Once the conductor passes this Wire Size planning screen, use the neighboring tools for the jobs they own:

  1. Inspect voltage drop in detailCheck a selected conductor, solve voltage-drop-only wire size, or calculate maximum distance.
  2. Size the OCPD separatelyBreaker/OCPD selection and coordination are not performed by Wire Size.
  3. Size the racewayUse the selected conductors to calculate raceway fill and minimum conduit size.

Related Calculators

Ohm's Law CalculatorVolts, amps, and resistance.Box Fill CalculatorBox capacity for the conductors.Cable Tray Fill CalculatorTray fill for cable runs.Watts Amps Volts CalculatorConvert watts and volts to current before sizing.

Wire sizing connects load, conductor conditions, voltage drop, protection, and raceway decisions without replacing those separate calculations. Browse the electrical calculator collection.

FAQ

What current should I enter?
Enter actual operating/load current before any continuous-load multiplier. Do not enter the breaker rating or a current you already multiplied by 125%. For balanced three-phase voltage-drop screening, enter line current.
What does continuous portion mean?
It is the part of the entered total current expected to be continuous. It is not extra current. The ordinary sizing requirement adds 25% of that portion, while the corrected/adjusted ampacity is still compared with the actual total current.
Why does the calculator ask for current-carrying conductors?
More than three applicable current-carrying conductors can reduce allowable ampacity. Neutral treatment depends on circuit/load configuration, while grounding and bonding conductors are not counted for this adjustment. Enter the applicable count for the installation.
Why can voltage drop choose a larger wire than ampacity?
A conductor may safely carry the current yet lose more voltage than the selected planning target over a long run. Wire Size can use a resistance-only screen to upsize the conductor, while detailed AC impedance or maximum-distance analysis remains in the dedicated Voltage Drop Calculator.
Does this calculator size breakers or grounding conductors?
No. Ordinary small-conductor protection limits are screened only where they constrain the conductor recommendation. Breaker/OCPD selection, equipment grounding conductor sizing, conduit fill, motors, HVAC, transformers, parallel conductors, and other special workflows remain outside this calculator.
Is the result code compliant?
It is a planning result under the supported 2026 NEC-based model and the inputs you provide, not complete code approval. Equipment listings, OCPD coordination, local code adoption/amendments, special circuits, and excluded installation conditions can change the final design.

Updated Sep 2026 · See our Methodology
Planning/sizing result for the supported single-conductor and copper NM-B workflows only. Final design still depends on the locally adopted NEC edition and amendments, equipment listings and termination ratings, OCPD coordination, actual circuit/load classification, installation conditions, and any special rules not modeled here. Parallel conductors, equipment grounding conductor sizing, dwelling-service reductions, motor/HVAC/transformer/tap rules, free-air/tray/duct-bank ampacity, flexible cords, specialty stranding, and other special applications are outside this calculator. AC voltage drop is a resistance-only approximation using a documented 75°C conductor-resistance basis.