About Contact

Voltage Drop Calculator

By · Updated Jul 2026

Estimate voltage drop by wire size, distance, and load current for 1-phase and 3-phase circuits.

V
A
ft

Your Voltage Drop Result

-
Voltage Drop (Percent)
-
Voltage Drop (Volts)
-
Pass/High vs Target
-
Selected Conductor
-
Upsize Suggestion
What This Result Means
Share

Copy and paste into any webpage:

Free to embed — credit to CalcShed.com appreciated.

How to Use
  1. Enter voltage - Use the circuit voltage (e.g. 120, 240, 480).
  2. Set amps - Enter the expected load current.
  3. Use one-way distance - For single-phase the formula internally accounts for the round trip.
  4. Choose wire size - Select the AWG you are considering.
  5. Pick a target - Compare against 3% (branch) or 5% (feeder + branch) - both are NEC recommendations, not hard limits.

Quick answer

A 20 amp load on 12 AWG copper at 120 volts loses 7.9 volts over a 100 foot one-way run - that is a 6.6 percent drop, more than double the 3 percent target, so you would step up to 8 AWG (about 2.6 percent). Put another way, 12 AWG is good for roughly 45 feet one-way at 20 amps and 120 volts before it reaches 3 percent. One thing worth knowing: the 3 percent figure is an NEC recommendation, not a hard rule - it lives in an Informational Note, not the enforceable text. Enter your voltage, load, wire, and run length above.

Where the Voltage Goes

Panel120 V sourceLoad20 Acurrent flow100 ft one-way run7.9 V lost in the wire (6.6%)~112 V arrives
Voltage drops steadily along the conductor as current fights its resistance. Here a 20 amp load pulls 120 volts at the panel down to about 112 volts at the load over a 100 foot one-way run on 12 AWG copper - a 7.9 volt, 6.6 percent drop. Longer runs, higher current, and smaller wire all increase it.

What Is Voltage Drop?

Voltage drop is the reduction in voltage that occurs as current flows through a conductor's resistance. Longer runs and higher current increase drop, and smaller wire sizes increase it even more.

This calculator estimates voltage drop for planning: enter voltage, amps, wire size, and run length to see the approximate drop and percent. For single-phase circuits the return path is part of the total loop length, which is why many formulas use a "2×" length factor.

Example: a 120V circuit carrying a heavy load over a long run can lose several volts on smaller wire. Upsizing the conductor or reducing the run length are the most direct ways to lower voltage drop.

Planning Targets People Use

These targets are commonly referenced in planning discussions:

Circuit TypeTypical TargetWhy It Matters
Branch circuit≈ 3%Helps motors start cleanly and reduces dimming
Feeder + branch total≈ 5%Keeps delivered voltage closer to equipment rating
Sensitive electronicsLower preferredReduces nuisance issues in long runs

Targets are planning guidelines. Your local rules and equipment tolerances may differ.

Formulas Used

This calculator uses standard resistance-based estimates:

1-phase = VD = 2 × I × R × L / 1000
Basis = Resistance from NEC Chapter 9 Table 8 at 75°C (K = 12.9 copper, 21.2 aluminum) - the standard for sizing under load.
3-phase = VD = √3 × I × R × L / 1000
Percent = %VD = (VD ÷ V) × 100

Code Notes & Sources

  • The 3 percent branch-circuit and 5 percent total voltage-drop figures are recommendations in an NEC Informational Note, not enforceable code. Many tools call them a code limit - they are guidance for good design, and the calculator treats them as selectable planning targets.NFPA 70 (NEC) 210.19(A) Informational Note - Voltage Drop
  • Conductor resistances used here come from the standard K-value field method (K = 12.9 for copper, 21.2 for aluminum), consistent with the direct-current resistance values in NEC Chapter 9 Table 8 at 75 degrees C.NFPA 70 (NEC) Chapter 9 Table 8 - Conductor Properties

Next Steps

If the drop is too high, the fix is usually a bigger wire. Then re-check the rest:

  1. Resize the conductorUpsize the wire to bring the drop under target, then confirm ampacity.
  2. Confirm the breakerMake sure the overcurrent device still matches the new conductor.
  3. Check the loadThe load current driving the drop starts with a proper load calculation.

Related Calculators

Amp to Wire Size CalculatorGauge from amperage.Ohms Law CalculatorResistance and voltage.Box Fill CalculatorBox cubic inches per NEC 314.16.Cable Tray Fill CalculatorTray fill percent check.

High voltage drop means you need a larger wire gauge. Browse the electrical calculator collection.

FAQ

Why does single-phase use a "2 ×" multiplier?
Single-phase circuits have an outgoing and return path, so the effective conductor length is doubled in the resistance calculation.
If voltage drop is high, what is the simplest fix?
The simplest fix is a bigger wire. Going up one wire size - for example 12 AWG to 10 AWG - drops resistance by roughly a third and cuts the voltage drop proportionally. Very long runs may need two or three sizes up. Running the load at a higher voltage helps most of all: 240 V instead of 120 V for the same wattage halves the current and so halves the drop.
What is acceptable voltage drop for a circuit?
The NEC recommends maximum 3% voltage drop for branch circuits and 5% total for the combined feeder and branch circuit. At 120V, 3% is 3.6V - so the endpoint should receive at least 116.4V. For sensitive equipment like computers and motors, keep drop under 2%. LED lighting and most modern electronics tolerate up to 5% without issues.
How far can you run 12 AWG wire on a 20 amp circuit?
At 120 V and a full 20 amp load, 12 AWG copper reaches the 3 percent target (3.6 V) at about 45 feet one-way. Stepping up to 10 AWG stretches that to roughly 72 feet, and 8 AWG to about 115 feet. Lighter loads run farther, since the drop scales with current. The calculator handles the exact math - enter your load, voltage, wire size, and run length.
Should I use load amps or breaker size for voltage drop?
Use the expected operating current (load amps) for a more accurate voltage drop estimate. Breaker size can be higher than the actual load, so using breaker amps can overstate the drop.

Updated Jul 2026 · See our Methodology
This calculator uses standard electrical formulas and published reference tables. Local codes and amendments vary. Use for planning estimates only. See our Data Sources and Methodology.