About Contact

Wire Size Calculator

By · Updated Jul 2026

Estimate a practical wire gauge (AWG) based on amps, conductor material, and wiring method (NM-B cable vs conduit).

A

Your Wire Size Estimate

-
Recommended Wire Size
-
Ampacity (table value)
-
Entered Load
-
Breaker (next standard size)
-
Assumptions
What This Result Means
Share

Copy and paste into any webpage:

Free to embed — credit to CalcShed.com appreciated.

How to Use
  1. Enter amperage - Use the expected load current in amps.
  2. Pick material - Copper and aluminum have different ampacity values.
  3. Pick the wiring method - NM-B cable (Romex) sizes from the 60°C column; THHN in conduit uses 75°C - the NEC 334.80 rule most tools skip.
  4. Review result - The calculator returns a smallest gauge that meets or exceeds the entered amps in the selected table.
  5. Confirm locally - Installation conditions can change allowable ampacity. Use this as a planning estimate.

Quick answer

For a 20 amp circuit you need 12 AWG copper; 30 amps takes 10 AWG; a 50 amp circuit is 8 AWG in conduit or 6 AWG for NM-B cable; and a 100 amp feeder uses 3 AWG copper or 1 AWG aluminum. The catch most calculators miss: NEC 240.4(D) caps the breaker on 14, 12, and 10 AWG copper at 15, 20, and 30 amps no matter what the ampacity table shows, and NM-B cable (Romex) must be sized from the 60 degree column per 334.80. Enter your load amps above and pick the wiring method for a size that respects both rules.

Bigger Load, Bigger Wire

AWGwire60°C75°C1415 A20 A1220 A25 A1030 A35 A840 A50 A655 A65 A385 A100 Amore amps needs a bigger wire (lower AWG number)
Copper conductor sizes from 14 AWG up to 3 AWG. A smaller AWG number means a physically thicker wire that carries more current. Each rung shows the NEC Table 310.16 ampacity at the 60 degree column (NM-B cable) and the 75 degree column (THHN in conduit).

How Do I Choose Wire Size?

Wire size is commonly planned around three things: load current (amps), conductor material (copper vs aluminum), and a reference ampacity table. This calculator returns a smallest gauge that meets or exceeds your input in the selected column as a starting point.

Real installs can change what's acceptable due to temperature, bundling, insulation type, terminations, and equipment limits. Treat this as a planning estimate and verify against your local code requirements and manufacturer specs before purchase or installation.

Example: a 50A load may point you toward a mid-range gauge in copper, but a long run can still require upsizing to reduce voltage drop. If distance is part of your project, run the same scenario through the Voltage Drop Calculator to sanity-check the result.

Wire Size vs Amp‑to‑Wire Size: Which Calculator Should You Use?

These two tools are close cousins, but they answer slightly different questions. Use the one that matches the decision you are making.

Use the Wire Size Calculator when you already know circuit amps (or breaker size) and want a practical gauge recommendation with copper vs aluminum and your wiring method (NM-B cable vs THHN in conduit).

Use the Amp‑to‑Wire Size Calculator when you are starting from an appliance/load amp draw and want a fast “what gauge is this roughly?” conversion before you refine the design.

For long runs or voltage‑sensitive loads, pair either result with the Voltage Drop Calculator.

The Two Rules Most Wire-Size Tools Miss

The first is NEC 240.4(D), the small-conductor rule. The ampacity table lists 14 AWG copper at 20 amps in the 75 degree column, but 240.4(D) still caps its breaker at 15 amps - and 12 AWG at 20, 10 AWG at 30 - regardless of the table. That is why a 20 amp circuit uses 12 AWG, never 14, even though the raw table makes 14 look sufficient. This calculator applies those caps, so it will not hand you a wire the code would reject.

The second is NEC 334.80: NM-B cable (the Romex in most home walls) is sized from the 60 degree column even though its insulation is stamped 90. Sizing Romex from the 75 degree column, which many tools do by default, overstates its capacity. Pick NM-B cable above and the calculator drops to 60 degrees automatically; pick THHN in conduit and it uses 75. The difference is real - a 50 amp circuit is 6 AWG in Romex but 8 AWG in conduit.

Copper vs Aluminum: Why the Gauge Changes

Copper and aluminum carry the same current differently. This quick table shows common planning pairings people compare:

Circuit ampsOften planned (copper)Often planned (aluminum)Notes
20 A12 AWG10 AWGAluminum typically needs a larger gauge.
30 A10 AWG8 AWGBigger gauge helps keep heating down.
50 A6 AWG4 AWGOften compared for larger loads.

Planning reference only. Always verify for your installation conditions and local code.

Quick Reference: Common Circuits

These are typical pairings people look up (planning reference only):

CircuitTypical BreakerOften Planned Wire (Cu)
Lighting circuit15 A14 AWG
General outlets20 A12 AWG
Small appliance circuit20 A12 AWG
Dryer / range branch30–50 A10–6 AWG
Subpanel feeder (small)60–100 A6–3 AWG

Your project may require a different choice depending on run length, voltage drop targets, and installation conditions.

How This Wire Size Result Is Chosen

Under the hood, this is a planning selection from common ampacity tables (you choose copper/aluminum and a wiring method, which sets the temperature column).

Pick rule = Choose the smallest gauge where table ampacity ≥ your input amps
Material effect = Aluminum typically needs a larger gauge than copper for the same amps
Next steps = If the run is long, verify voltage drop separately

This is sizing guidance for estimates and comparisons. Installation method, bundling, insulation rating, and terminations can change the required wire.

Code Notes & Sources

  • Conductor ampacities here follow NEC Table 310.16 for copper and aluminum at the 60, 75, and 90 degree columns. Which column applies depends on the wiring method and equipment terminal ratings, not the wire alone.NFPA 70 (NEC) Table 310.16 - Conductor Ampacity
  • The small-conductor rule caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG copper, whatever the ampacity table shows. This calculator enforces those limits.NFPA 70 (NEC) 240.4(D) - Small Conductors
  • NM-B cable is sized from the 60 degree C column even though its conductors carry 90 degree insulation, which is why the wiring-method selector changes the answer.NFPA 70 (NEC) 334.80 - NM Cable Ampacity

Next Steps

Wire size is one input in the circuit. Check the rest:

  1. Check the run lengthA long run can force a bigger wire than ampacity alone - verify voltage drop.
  2. Size the breakerMatch the overcurrent device to the load and the conductor.
  3. Size the conduitOnce you know the wire, check how many fit in the raceway at 40 percent fill.

Related Calculators

Amp to Wire Size CalculatorGauge straight from amps.Electrical Load CalculatorLoad on the wire.Box Fill CalculatorBox cubic inches per NEC 314.16.Cable Tray Fill CalculatorTray fill percent check.

Wire size depends on amperage, distance, and voltage. Browse the full electrical calculator collection.

FAQ

Is this wire size result code-compliant?
This tool is for planning estimates. Installation conditions and local code rules can change allowable ampacity. Always verify with the rules and equipment ratings that apply to your project.
Why do copper and aluminum give different wire sizes?
Aluminum has higher electrical resistance than copper - about 1.6× higher - so a larger aluminum wire is needed to carry the same current with the same voltage drop. Aluminum is cheaper and lighter, making it common for service entrance conductors and large feeder runs. For branch circuits inside homes, copper is standard. Aluminum connections require anti-oxidant compound and aluminum-rated terminals.
What wire size do I need for a 50 amp circuit?
A 50 amp circuit uses 8 AWG copper in conduit (THHN, 75 degree column) or 6 AWG copper for NM-B cable (Romex, 60 degree column); aluminum would be 6 AWG in conduit. That split is exactly why the calculator asks for your wiring method - a common 50 amp range or EV charger run in Romex needs the larger 6 AWG. The circuit takes a double-pole 50 amp breaker either way. Always verify local requirements - some applications also require GFCI protection or specific insulation.
What is the difference between AWG and wire gauge in mm²?
AWG (American Wire Gauge) is used in the US and Canada. European and international standards use mm² cross-sectional area. Common conversions: 14 AWG ≈ 2.5mm², 12 AWG ≈ 4mm², 10 AWG ≈ 6mm², 8 AWG ≈ 10mm², 6 AWG ≈ 16mm². When working with imported equipment or international specifications, always convert to ensure correct wire selection.
Why does the calculator ask NM-B cable vs conduit?
Because NEC 334.80 sizes NM-B cable (Romex) from the 60 degree column while THHN and THWN in conduit use the 75 degree column. Same copper, different allowable ampacity: 12 AWG NM-B is good for 20 amps, but 12 AWG THHN in conduit reaches 25. Most quick calculators ignore this and use 75 for everything, which overstates Romex. Picking the method here gives the size an inspector will actually expect.
Do I need to size wire differently for continuous loads?
For planning, many people treat long‑running loads as “continuous” and keep sustained current below roughly 80% of breaker rating. Local codes differ, so treat this as a sizing sanity‑check and confirm with an electrician or your jurisdiction.

Updated Jul 2026 · See our Methodology
This calculator uses standard electrical formulas and published reference tables. Local codes and amendments vary. Use for planning estimates only. See our Data Sources and Methodology.