Voltage Drop Calculator
Check voltage drop, find a voltage-drop-only conductor size, or solve the maximum run length for a target percentage.
How to Use
- Choose the question - Check a selected conductor, find the first configured AWG that meets the drop target, or solve the maximum one-way run length for a selected conductor.
- Enter operating current - Use the expected current flowing during operation, not automatically the breaker rating.
- Measure one-way distance - Enter source-to-load distance. The calculator applies the return-path factor internally for single-phase/DC and the √3 relationship for balanced three-phase.
- Keep ampacity separate - The minimum-wire mode is a voltage-drop screen only. A conductor still has to pass ampacity, termination, adjustment, equipment, and code checks.
- Treat 3% and 5% as design guidance - They are common planning targets associated with NEC informational-note guidance, not universal hard limits for every installation.
At 120 V, 20 A, 100 ft one-way, 12 AWG copper is about 6.6% drop in this resistance-based model. The first configured conductor below a 3% target is 8 AWG at about 2.6%. If you keep 12 AWG, the 3% one-way distance is about 45.6 ft. The calculator can solve all three versions directly.
Three Ways to Use Voltage Drop
What the Result Includes
Check mode shows percent drop, volts lost, estimated load-end voltage, target status, a larger configured conductor when needed, and the maximum distance the selected wire can run before reaching the target.
Minimum-wire mode starts at the smallest configured AWG and moves upward until the resistance-based voltage-drop result meets the selected target. That answer is not an ampacity recommendation. Use the Wire Size Calculator for a combined ampacity and voltage-drop screen.
Maximum-distance mode rearranges the same equation to solve one-way run length. It is useful when the conductor is already fixed and the design question is how far that conductor can carry the expected current before reaching the chosen drop budget.
Formulas Used
Resistance values are expressed in ohms per 1,000 ft and distance is one-way:
Balanced three-phase = VD = √3 × I × R × L ÷ 1000
Percent drop = VD% = VD ÷ system voltage × 100
Load-end voltage = V_load = V_source − VD
Maximum distance = L = (V × target% ÷ 100) × 1000 ÷ (factor × I × R)
This is a resistance-only model. It deliberately does not pretend that AC reactance, raceway material, power factor, parallel conductors, or every installation condition is included.
Example: 20 A, 120 V, Copper, 3% Target
| Wire | Drop at 100 ft | Approx. max one-way run at 3% |
|---|---|---|
| 12 AWG | 6.59% | 45.6 ft |
| 10 AWG | 4.14% | 72.4 ft |
| 8 AWG | 2.60% | 115.2 ft |
| 6 AWG | 1.64% | 183.1 ft |
Resistance-based planning example using the configured conductor resistance data. Ampacity is not evaluated in this table.
Code and Technical Sources
- NEC branch-circuit voltage-drop guidance appears in an informational note describing 3% at the farthest outlet and 5% total feeder-plus-branch-circuit drop as reasonable design guidance, rather than a universal hard limit for every installation.NFPA 70 development record for 210.19 voltage-drop guidance
- Voltage drop remains separate from ampacity. NEC Table 310.16 provides conductor ampacity references, while final conductor sizing can also depend on adjustment/correction, terminations, equipment rules, and the adopted code.NFPA 70 Table 310.16 development record
Next Steps
Voltage drop is only one conductor check:
Related Calculators
Voltage drop is one part of circuit design. Browse the electrical calculator collection.