About Contact

Voltage Drop Calculator

By CalcShed Editorial Team · Updated Apr 2026

Estimate voltage drop by wire size, distance, and load current for 1-phase and 3-phase circuits.

V
A
ft

Your Voltage Drop Result

Voltage Drop (Percent)
Voltage Drop (Volts)
Pass/High vs Target
Selected Conductor
Upsize Suggestion
What This Result Means
How to Use
  1. Enter voltage — Use the circuit voltage (e.g. 120, 240, 480).
  2. Set amps — Enter the expected load current.
  3. Use one-way distance — For single-phase the formula internally accounts for the round trip.
  4. Choose wire size — Select the AWG you are considering.
  5. Check percent drop — Compare to a planning target (commonly 3% branch circuits).

What Is Voltage Drop?

Voltage drop is the reduction in voltage that occurs as current flows through a conductor's resistance. Longer runs and higher current increase drop, and smaller wire sizes increase it even more.

This calculator estimates voltage drop for planning: enter voltage, amps, wire size, and run length to see the approximate drop and percent. For single-phase circuits the return path is part of the total loop length, which is why many formulas use a "2×" length factor.

Example: a 120V circuit carrying a heavy load over a long run can lose several volts on smaller wire. Upsizing the conductor or reducing the run length are the most direct ways to lower voltage drop.

Planning Targets People Use

These targets are commonly referenced in planning discussions:

Circuit TypeTypical TargetWhy It Matters
Branch circuit≈ 3%Helps motors start cleanly and reduces dimming
Feeder + branch total≈ 5%Keeps delivered voltage closer to equipment rating
Sensitive electronicsLower preferredReduces nuisance issues in long runs

Targets are planning guidelines. Your local rules and equipment tolerances may differ.

Formulas Used

This calculator uses standard resistance-based estimates:

1-phase = VD = 2 × I × R × L / 1000
3-phase = VD = √3 × I × R × L / 1000
Percent = %VD = (VD ÷ V) × 100

Related Calculators

High voltage drop means you need a larger wire gauge. Browse the electrical calculator collection.

FAQ

Why does single-phase use a "2 ×" multiplier?

Single-phase circuits have an outgoing and return path, so the effective conductor length is doubled in the resistance calculation.

If voltage drop is high, what is the simplest fix?

The simplest fix is to increase wire size. Going up one AWG size (e.g., from 12 AWG to 10 AWG) reduces resistance by about 25% and cuts voltage drop proportionally. For very long runs (100+ feet), you may need to go up two or three AWG sizes. Running a higher voltage (240V instead of 120V for the same load) also cuts voltage drop in half because current is halved.

What is acceptable voltage drop for a circuit?

The NEC recommends maximum 3% voltage drop for branch circuits and 5% total for the combined feeder and branch circuit. At 120V, 3% is 3.6V — so the endpoint should receive at least 116.4V. For sensitive equipment like computers and motors, keep drop under 2%. LED lighting and most modern electronics tolerate up to 5% without issues.

How far can you run 12 AWG wire on a 20 amp circuit?

For a 20A circuit at 120V with a 3% maximum voltage drop (3.6V), 12 AWG copper can run approximately 50–60 feet one-way before voltage drop becomes significant. For runs up to 100 feet, use 10 AWG. For 150 feet, use 8 AWG. The calculator above handles this math precisely — enter your load, voltage, wire size, and run length for an exact result.

Should I use load amps or breaker size for voltage drop?

Use the expected operating current (load amps) for a more accurate voltage drop estimate. Breaker size can be higher than the actual load, so using breaker amps can overstate the drop.


Reviewed Apr 2026 · See our Methodology
This calculator uses standard electrical formulas and published reference tables. Local codes and amendments vary. Use for planning estimates only. See our Data Sources and Methodology.