Power Factor Calculator
Solve kW, kVA, kVAR and power factor from the values you have, or calculate the capacitive kVAR needed to improve a lagging load.
Help improve this calculator
Report an issue or suggest an improvement.
For: Power Factor Calculator
How to Use
- Choose the values you have - start with kW+kVA, kW+kVAR, kVA+kVAR, kW+known PF, or measured kW+volts+amps. The calculator fills in the remaining power-triangle values.
- Label leading or lagging separately - power factor magnitude alone does not tell you reactive direction. Use lagging for inductive loads and leading for capacitive direction when that is known.
- Use correction mode only for lagging loads - enter kW, current lagging PF, and target PF. Voltage is optional and adds line-current and ideal-capacitance context.
- Treat µF as an ideal equivalent - real capacitor-bank selection depends on rated voltage, frequency, switching, harmonics, resonance, tolerance, duty, protection, and manufacturer data.
Electrical power factor is PF = kW ÷ kVA = cos φ for the sinusoidal/displacement power triangle. A 75 kW load drawing 90 kVA has PF ≈ 0.8333, reactive-power magnitude ≈ 49.75 kVAR, and phase-angle magnitude ≈ 33.56°. A 100 kW lagging load corrected from PF 0.80 to 0.95 needs about 42.13 kVAR of capacitive correction.
The Electrical Power Triangle
How to Calculate Power Factor From Available Readings
The readings you have determine which calculation is possible. Select the matching mode instead of supplying a guessed value.
kW and kVA: Divide real power by apparent power to find PF magnitude.
kW and kVAR: Calculate apparent kVA from the power triangle, then divide kW by kVA.
kVA and kVAR: Calculate real kW from the power triangle, then divide by kVA.
kW, voltage, and current: With RMS voltage and current measured for the same load at the same operating point, apparent kVA = V × A ÷ 1,000 for single-phase, or √3 × line-to-line V × line A ÷ 1,000 for a balanced three-phase system. Do not combine readings from different loads or time periods. Divide measured kW by the resulting kVA.
Voltage and current only: These readings give apparent power, but are not enough to determine PF without real kW or another independent power reading.
Known PF or correction: With kW and an existing PF, solve for kVA and kVAR. For a lagging load with known starting PF, correction mode estimates the capacitive kVAR needed to reach a specified target PF; it cannot determine an unknown starting PF.
Measured kW divided by measured kVA gives true power-factor magnitude, including the effect of waveform distortion. The power-triangle calculations involving kVAR and the equality PF = cos φ assume sinusoidal conditions; for distorted waveforms, the displayed kVAR and angle are model estimates, not harmonic measurements. To calculate PF for several loads together, use simultaneous total kW and kVA readings at the same supply point. Adding individual kVA magnitudes does not generally give the combined apparent power.
Power Triangle Examples
| Real power | Apparent power | Power factor | Reactive-power magnitude |
|---|---|---|---|
| 50 kW | 50 kVA | 1.000 | 0 kVAR |
| 50 kW | 62.5 kVA | 0.800 | 37.5 kVAR |
| 75 kW | 90 kVA | 0.833 | 49.75 kVAR |
| 100 kW | 111.11 kVA | 0.900 | 48.43 kVAR |
Reactive magnitude is Q = √(S² − P²). Lagging/leading direction is a separate property.
Power-Factor Correction
For a lagging inductive load, correction kVAR is calculated from Qc = P × (tan φ1 − tan φ2), where φ1 = arccos(PF1) and φ2 = arccos(PF2). Real kW stays constant while reactive demand, apparent kVA, and line current fall.
If system voltage is entered, correction mode also compares line current before and after. It additionally reports the correction-bank line-current magnitude and an ideal capacitance equivalent for the chosen frequency. For three-phase banks, Delta and Wye capacitance are different because individual capacitors see different voltages.
That ideal µF value is not a purchase recommendation. Harmonics, resonance, switching steps, load variation, system short-circuit strength, capacitor voltage rating, tolerances, and manufacturer application guidance can require a detuned, filtered, automatic, or otherwise engineered system.
Power-Factor Correction Multiplier Reference
| Current PF | To 0.90 PF | To 0.95 PF | To 0.98 PF |
|---|---|---|---|
| 0.60 | 0.849 kVAR/kW | 1.005 kVAR/kW | 1.130 kVAR/kW |
| 0.65 | 0.685 | 0.840 | 0.966 |
| 0.70 | 0.536 | 0.692 | 0.817 |
| 0.75 | 0.398 | 0.553 | 0.679 |
| 0.80 | 0.266 | 0.421 | 0.547 |
| 0.85 | 0.135 | 0.291 | 0.417 |
| 0.90 | N/A | 0.156 | 0.281 |
Multiply load kW by the factor to estimate required capacitive kVAR. Values are formula-derived from tan(arccos(PFcurrent)) − tan(arccos(PFtarget)); a dash means the listed target is not above the current PF.
Worked Correction Example: 100 kW, PF 0.80 → 0.95
| Quantity | Before | After / correction |
|---|---|---|
| Apparent power | 125.00 kVA | 105.26 kVA |
| Reactive power | 75.00 kVAR | 32.87 kVAR |
| Capacitive correction | N/A | 42.13 kVAR |
| Phase angle | 36.87° | 18.19° |
| 480 V 3φ line current | 150.35 A | 126.63 A |
The line-current row assumes balanced 480 V three-phase. Actual capacitor equipment still requires application engineering.
When a Capacitor-Only Answer Needs More Review
Capacitor kVAR can be calculated from the power triangle, but that does not prove that a plain capacitor bank is suitable for the system. Nonlinear loads such as variable-frequency drives and rectifiers can interact with capacitors and system inductance at harmonic frequencies.
Eaton's plant-engineer guide uses the ratio of total three-phase nonlinear-load kVA to the main transformer kVA as a screening indicator. It says plain capacitors can usually be applied without problems below 15%, harmonic filters will almost always be required above 25%, and systems between those values need other factors considered.
Those percentages are Eaton application guidance, not a universal pass/fail rule. Harmonic measurements, system short-circuit strength, utility requirements, switching method, and equipment manufacturer guidance still control the final design.
Power Factor and Correction Formulas
The core relationships used by the calculator are:
Apparent power = kVA = √(kW² + kVAR²)
Reactive magnitude = kVAR = √(kVA² − kW²)
Phase angle = φ = arccos(PF)
Single-phase apparent power = kVA = V × I ÷ 1000
Balanced three-phase apparent power = kVA = √3 × VLL × I ÷ 1000
Correction kVAR = Qc = kW × [tan(arccos PF1) − tan(arccos PF2)]
Single-phase ideal capacitance = C = Q ÷ (2πfV²)
3φ Delta ideal capacitance per capacitor = C = Qtotal ÷ (3 × 2πfVLL²)
3φ Wye ideal capacitance per phase = C = Qtotal ÷ (2πfVLL²)
The power-triangle phase-angle relationships assume sinusoidal conditions. In the ideal-capacitance equations, Q and Qtotal must be expressed in VAR (1 kVAR = 1,000 VAR), V in volts and f in hertz; C is in farads (1 F = 1,000,000 µF). The calculator handles these unit conversions internally. The result is an ideal steady-state equivalent, not a capacitor-bank selection; follow manufacturer and system-study requirements.
Authoritative Technical Sources
- Fluke defines power factor as the ratio of working power in kW to apparent power in kVA and explains the relationship between power factor, kVA, current, and system loading.Fluke - Power Factor: What it is and How to Calculate it
- Eaton publishes the kW/kVA/kVAR relationships, current and capacitor formulas, correction method, and harmonic-screening guidance used to decide when plain capacitors may need a deeper system review.Eaton - Power factor correction: A guide for the plant engineer
- Schneider Electric provides an official power-factor-correction calculator/tool intended to estimate capacitor kVAR required to improve the power factor of a load or system.Schneider Electric USA - Power Factor Correction Calculator
Next Steps
Use the result in the next electrical calculation that needs it:
Related Calculators
Power factor connects real power, apparent power, reactive power, and current. Browse the electrical calculator collection for conversion, load, transformer, conductor, and protection tools.