Skip to main content

Power Factor Calculator

By · Updated Aug 2026

Solve kW, kVA, kVAR and power factor from the values you have, or calculate the capacitive kVAR needed to improve a lagging load.

kW
kVA
kVAR
PF
Choose lagging for inductive reactive power or leading for capacitive reactive power when the direction is known.
V
Required for measured kW + volts + amps. Optional in correction mode, where voltage adds current and ideal-capacitance details.
A
PF
PF
Use the target required by the project, utility, or equipment study. Do not assume that 1.00 is always the best target.
Share

How to Use

  1. Choose the values you have - start with kW+kVA, kW+kVAR, kVA+kVAR, kW+known PF, or measured kW+volts+amps. The calculator fills in the remaining power-triangle values.
  2. Label leading or lagging separately - power factor magnitude alone does not tell you reactive direction. Use lagging for inductive loads and leading for capacitive direction when that is known.
  3. Use correction mode only for lagging loads - enter kW, current lagging PF, and target PF. Voltage is optional and adds line-current and ideal-capacitance context.
  4. Treat µF as an ideal equivalent - real capacitor-bank selection depends on rated voltage, frequency, switching, harmonics, resonance, tolerance, duty, protection, and manufacturer data.

Quick answer

Electrical power factor is PF = kW ÷ kVA = cos φ for the sinusoidal/displacement power triangle. A 75 kW load drawing 90 kVA has PF ≈ 0.8333, reactive-power magnitude ≈ 49.75 kVAR, and phase-angle magnitude ≈ 33.56°. A 100 kW lagging load corrected from PF 0.80 to 0.95 needs about 42.13 kVAR of capacitive correction.

The Electrical Power Triangle

P · Real power (kW)Q · Reactive power(kVAR)S · Apparent power (kVA)φPF = P ÷ S = cos φ
Real power and reactive power form the two perpendicular sides; apparent power is the diagonal. Power factor is the ratio P ÷ S. Lagging or leading direction is reported separately.

Solve Power Factor From the Values You Have

Different meters, nameplates, and studies provide different combinations of kW, kVA, kVAR, voltage, current, and PF. Choose the mode that matches the values in front of you and the calculator returns the remaining power-triangle quantities.

For measured voltage/current mode, single-phase apparent power is V × I and balanced three-phase apparent power is √3 × VLL × I. Real kW divided by that kVA gives the power-factor magnitude.

The formulas describe the sinusoidal/displacement power triangle. Nonlinear loads can have distortion power factor, so a power-quality analyzer may report total PF that cannot be reconstructed from a simple phase angle alone.

If several equipment loads need to be combined before you evaluate the aggregate power relationship, use the Electrical Load Calculator first to total the known W or VA values.

Power Triangle Examples

Real powerApparent powerPower factorReactive-power magnitude
50 kW50 kVA1.0000 kVAR
50 kW62.5 kVA0.80037.5 kVAR
75 kW90 kVA0.83349.75 kVAR
100 kW111.11 kVA0.90048.43 kVAR

Reactive magnitude is Q = √(S² − P²). Lagging/leading direction is a separate property.

Power-Factor Correction

For a lagging inductive load, correction kVAR is calculated from Qc = P × (tan φ1 − tan φ2), where φ1 = arccos(PF1) and φ2 = arccos(PF2). Real kW stays constant while reactive demand, apparent kVA, and line current fall.

If system voltage is entered, correction mode also compares line current before and after. It additionally reports the correction-bank line-current magnitude and an ideal capacitance equivalent for the chosen frequency. For three-phase banks, Delta and Wye capacitance are different because individual capacitors see different voltages.

That ideal µF value is not a purchase recommendation. Harmonics, resonance, switching steps, load variation, system short-circuit strength, capacitor voltage rating, tolerances, and manufacturer application guidance can require a detuned, filtered, automatic, or otherwise engineered system.

Power-Factor Correction Multiplier Reference

Current PFTo 0.90 PFTo 0.95 PFTo 0.98 PF
0.600.849 kVAR/kW1.005 kVAR/kW1.130 kVAR/kW
0.650.6850.8400.966
0.700.5360.6920.817
0.750.3980.5530.679
0.800.2660.4210.547
0.850.1350.2910.417
0.90N/A0.1560.281

Multiply load kW by the factor to estimate required capacitive kVAR. Values are formula-derived from tan(arccos(PFcurrent)) − tan(arccos(PFtarget)); a dash means the listed target is not above the current PF.

Worked Correction Example: 100 kW, PF 0.80 → 0.95

QuantityBeforeAfter / correction
Apparent power125.00 kVA105.26 kVA
Reactive power75.00 kVAR32.87 kVAR
Capacitive correctionN/A42.13 kVAR
Phase angle36.87°18.19°
480 V 3φ line current150.35 A126.63 A

The line-current row assumes balanced 480 V three-phase. Actual capacitor equipment still requires application engineering.

When a Capacitor-Only Answer Needs More Review

Capacitor kVAR can be calculated from the power triangle, but that does not prove that a plain capacitor bank is suitable for the system. Nonlinear loads such as variable-frequency drives and rectifiers can interact with capacitors and system inductance at harmonic frequencies.

Eaton's plant-engineer guide uses the ratio of total three-phase nonlinear-load kVA to the main transformer kVA as a screening indicator. It says plain capacitors can usually be applied without problems below 15%, harmonic filters will almost always be required above 25%, and systems between those values need other factors considered.

Those percentages are Eaton application guidance, not a universal pass/fail rule. Harmonic measurements, system short-circuit strength, utility requirements, switching method, and equipment manufacturer guidance still control the final design.

Power Factor and Correction Formulas

The core relationships used by the calculator are:

Power factor = PF = kW ÷ kVA = cos φ
Apparent power = kVA = √(kW² + kVAR²)
Reactive magnitude = kVAR = √(kVA² − kW²)
Phase angle = φ = arccos(PF)
Single-phase apparent power = kVA = V × I ÷ 1000
Balanced three-phase apparent power = kVA = √3 × VLL × I ÷ 1000
Correction kVAR = Qc = kW × [tan(arccos PF1) − tan(arccos PF2)]
Single-phase ideal capacitance = C = Q ÷ (2πfV²)
3φ Delta ideal capacitance per capacitor = C = Qtotal ÷ (3 × 2πfVLL²)
3φ Wye ideal capacitance per phase = C = Qtotal ÷ (2πfVLL²)

Capacitance formulas produce ideal steady-state equivalents. Real bank rating and application must follow equipment/manufacturer and system-study requirements.

Authoritative Technical Sources

Next Steps

Use the result in the next electrical calculation that needs it:

  1. Convert apparent power to currentUse kVA and voltage directly when current is the next value you need.
  2. Size the conductor after current is knownApply ampacity and installation conditions rather than treating PF alone as conductor sizing.

Related Calculators

Transformer CalculatorApply load kW, PF, and kVA to transformer capacity planning.Watts Amps Volts CalculatorSolve real power, current, and voltage for AC systems.Generator Size CalculatorCompare running and starting source-capacity requirements.Ohm's Law CalculatorReview the underlying voltage-current-power relationships for simple circuits.Breaker Size CalculatorKeep overcurrent protection separate from power-factor analysis.

Power factor connects real power, apparent power, reactive power, and current. Browse the electrical calculator collection for conversion, load, transformer, conductor, and protection tools.

FAQ

Is power factor always kW divided by kVA?
For the measured real and apparent power of an AC load, PF magnitude is kW/kVA. In sinusoidal linear systems it also equals cos φ. Nonlinear loads can have distortion power factor, so total PF is not always explained by phase angle alone.
What is the difference between lagging and leading power factor?
Lagging PF is commonly associated with inductive reactive demand; leading PF is associated with capacitive direction. The same PF magnitude can describe either, so this calculator keeps direction explicit.
How many kVAR are needed to improve PF from 0.80 to 0.95?
The multiplier is about 0.4213 kVAR per kW. A 100 kW lagging load therefore needs about 42.13 kVAR of capacitive correction in the ideal steady-state calculation.
Can I buy a capacitor bank from the µF result?
No. The µF result is an ideal electrical equivalent. Real capacitor-bank selection must account for voltage rating, frequency, harmonics, resonance, switching, duty, protection, manufacturer instructions, and the actual system.
Why does correcting PF reduce current?
At fixed real kW and voltage, improving lagging PF reduces apparent kVA. Because line current is proportional to kVA at fixed voltage and phase, the upstream current supplying the corrected system falls.

Updated Aug 2026 · See our Methodology
Electrical power-factor planning tool. Power-triangle modes use sinusoidal/displacement relationships; nonlinear loads can require measured total power factor and harmonic analysis. Correction mode assumes a lagging inductive load and steady real kW. Optional capacitance is an ideal equivalent, not capacitor-bank selection. Verify utility requirements, system harmonics/resonance, switching, protection, equipment ratings, and final design with qualified electrical professionals and manufacturer data.